Becsys5 Installation And Technical Manual -

| Parameter | Value | |-----------|-------| | Supply voltage | 24V DC ±20% | | Max power consumption | 60W (base) / 120W (fully loaded) | | Inrush current | <20A for 1ms | | Isolation | 1500V AC (input to ground) |

This manual provides step-by-step instructions and technical specifications for the installation, initial configuration, and ongoing technical maintenance of the BECSys5 Building Energy Control System. It is intended for certified electrical technicians, system integrators, and facility engineers. becsys5 installation and technical manual

  • Record serial numbers of MCM and PSU.
  • Each point requires a unique object identifier within the BACnet device. Naming convention: [Equipment]_[PointType]_[Function]. | Parameter | Value | |-----------|-------| | Supply

    Example for an AHU supply air temperature sensor: Record serial numbers of MCM and PSU

    To create points via web UI:

    Access via front panel or serial console (115200, 8‑N‑1).
    Set static IP (DHCP not recommended for production):

    IP Address   : 192.168.1.100
    Subnet Mask  : 255.255.255.0
    Default GW   : 192.168.1.1
    BACnet Port  : 47808 (UDP)
    Modbus TCP Port : 502